Contact
Tel: 18037961302
Sales hot line ( 24 hours  service): 18037961302

E-Mail: firstfurnace@gmail.com

whatsapp:+8618037961302

Adress: Luoxin Industrial Park, Luoyang, Henan
  • Products
  • 2T Induction Melting Furnace

    1T Induction Melting Furnace

    500kg Induction Melting Furnac

    250kg Induction Melting Furnac

    Induction Melting Furnace

    3 T Induction Melting Furnace

    5T Induction Melting Furnace

    1T One Belt Two Intermediate F

    5T One Belt Two Intermediate F

    3T One Belt Two Intermediate F

    2T One Belt Two Intermediate F

    5T Parallel Intermediate Frequ

    5T Intermediate Frequency Furn

    5T Series Intermediate Frequen

    3T Series Intermediate Frequen

    2T Series Intermediate Frequen

    1T Series Intermediate Frequen

    0.5T Series Intermediate Frequ

    0.25T Series Intermediate Freq

    1T Parallel Intermediate Frequ

    2T Parallel Intermediate Frequ

    0.5T Parallel Intermediate Fre

    0.25T Parallel Intermediate Fr

    Parallel Intermediate Frequenc

    3T Intermediate Frequency Furn

    2 T Intermediate Frequency Fur

    1T Intermediate Frequency Furn

    0.25T Intermediate Frequency F

    Industrial electric furnace technical information
        

    Detection of main components of induction melting furnace

    SCR detection method


    Use a digital multimeter 200KΩ to measure the thyristor forward and reverse resistance, which should be between 3KΩ and 100KΩ (the resistance is affected by the water circuit and the parallel voltage equalization resistance).

    Use a digital multimeter 200Ω to measure the thyristor gate resistance, which should be between 10Ω and 30Ω.

    Capacitor detection method

    Disconnect the connecting copper bars of the capacitor. Use an insulated shaker to test whether each column of each capacitor is charged and discharged, and it should be able to charge and discharge normally.

    Induction melting furnace detection method

    Observe whether the short circuit is short between the turns: whether the coil is insulated from the protective ground. Induction coils are short-circuited between turns, and such faults are particularly prone to occur in small-sized medium-frequency induction furnaces. Because the furnace is small, it is deformed by thermal stress during operation, resulting in a short circuit between turns, and the fault is characterized by a large current and a higher operating frequency than usual. .

    The induction coil leaks water, which may cause the coil to ignite between the turns, and must be repaired in time to run.

    The molten steel sticks to the induction coil, and the steel slag is hot and red, which will cause the copper tube to burn through and must be cleaned up in time.